B+C three phase Metal oxide varistor Surge arrestor, surge protection 60KA HS2-60

Application AC/DC distribution Power supplies Industrial automation Telecommunications Motor controls systems PLC applications Power transfer equipment HVAC applications AC drives UPS systems Security systems IT / Data centers Medical equipment

Products Details

Features/Benefifits
Easy installation or retrofifit
Din-rail mountable
Fail-safe /self-protected design
Remote indicator (optional) with 3 pin NO/NC contact
IP20 fifinger-safe design
Visual indicator
Small foot print
Plug-in format
HS25-B60 is the range of devices for discharging induced transient overvoltages (Type 1+2 / Class I+II), in accordance with EN/IEC 61643-11. DIN rail plug-in format.
Ability to discharge lightning currents (10/350μs) and induced voltage surges (8/20 μs).
■Suitable for the second stage of protection in supply distribution panels.
■Discharge capacity with an 8/20 μs waveform. Imax: 60 kA.
■Exclusive devices for TNS, TNC, TT , IT earthing systems.
■Exclusive devices which are compatible with Power Line Communication networks.
■Biconnect - two types of terminal: for rigid or flflexible cable and for fork type comb busbar.
■Available with optional remote signalling.
Data sheet
TypeTechnical DataMaximum continuous voltage (UC) (L-N)

HS25-B60

 

275 / 320 / 385 / 420V

Maximum continuous voltage (UC) (N-PE)

275V

SPD to EN 61643-11, SPD to IEC 61643-11

Type 1+2 , class I+II

Lightning impulse current (10/350μs) (Iimp)

12.5kA

Nominal discharge current (8/20μs) (In)

30kA

Maximum discharge current (8/20μs) (Imax)

60kA

Voltage protection level (Up) (L-N)

≤ 1.5 / 1.8 / 2.0 / 2.2kV

Voltage protection level (Up) (N-PE)

≤ 1.5kV

Response time (tA) (L-N)

< 25ns

Response time (tA) (N-PE)

< 100ns

Thermal Protection

YES

Operating State/Fault Indication

Green (good) / White or Red (replace)

Degree of protection

IP 20

Insulating material / flammability class

PA66,UL94 V-0

Temperature range

-40ºC~+80ºC

Altitude

13123 ft [4000m]

Conductor Cross Section (max)

35mm2 (Solid) / 25mm2 (Flexible)

Remote Contacts (RC)

Optional

Format

Pluggable

For mounting on

DIN rail 35mm

Place of installation

indoor installation

Dimensions

HS2-60 Power Surge Protector 001

1. product design standard: this product is designed according to relevant international standards IEC, and its performance meets the requirements of national standard GB 18802.1-2011 "low voltage surge protector (SPD) part 1: performance requirements and test methods of surge protector for low voltage distribution system". 2. Scope of product use: GB50343-2012 Technical Code for Lightning Protection of Building Electronic Information System 3 Selection of surge protector: The primary SPD must be set in the main distribution box at the entrance of building power supply. 4. Product features: This product has the characteristics of low residual voltage, fast response speed, large current capacity (impulse current Iimp(10/350μs) is 25kA/ line, long service life, simple maintenance and convenient installation, etc. 5.Working temperature: -25℃ ~+70℃, working humidity: 95%. Quality assurance: 1. Strict control on choose of the raw material sources. 2. Speciific technology guide for the production of each product. 3. Completed quality testing system for the semi-finished products and finised products.