wholesale 3 phase 10-20ka 385V SPD,overvoltage Power surge protection,lightning protection class II+III spd HS2-10

Application AC/DC distribution Power supplies Industrial automation Telecommunications Motor controls systems PLC applications Power transfer equipment HVAC applications AC drives UPS systems Security systems IT / Data centers Medical equipment

Products Details

Features/Benefifits Easy installation or retrofit Din-rail mountable Fail-safe /self-protected design Remote indicator (optional) with 3 pin NO/NC contact IP20 finger-safe design Visual indicator Small foot print
Data sheet

Type

HS25-D10

Technical Data

Maximum continuous voltage (UC) (L-N)

275 / 320 / 385 / 420V

Maximum continuous voltage (UC) (N-PE)

275V

SPD to EN 61643-11

Type 3

SPD to IEC 61643-11

class III

Nominal discharge current (8/20μs) (In)

5kA

Maximum discharge current (8/20μs) (Imax)

10kA

Voltage protection level (Up) (L-N)

≤ 1.0 / 1.1/ 1.3 / 1.5kV

Voltage protection level (Up) (N-PE)

≤ 1.5kV

Response time (tA) (L-N)

< 25ns

Response time (tA) (N-PE)

< 100ns

Thermal Protection

YES

Operating State/Fault Indication

Green (good) / White or Red (replace)

Degree of protection

IP 20

Insulating material / flammability class

PA66,UL94 V-0

Temperature range

-40ºC~+80ºC

Altitude

13123 ft [4000m]

Conductor Cross Section (max)

35mm2 (Solid) / 25mm2 (Flexible)

Remote Contacts (RC)

Optional

Format

Pluggable

For mounting on

DIN rail 35mm

Place of installation

indoor installation

Plug-in format
HS25-D10 is the range of devices for discharging induced transient overvoltages(Type 3 / Class III), in accordance with EN/IEC 61643-11. DIN rail plug-in format. Ability to discharge induced voltage surges (8/20 μs). For very fine protection of sensitive equipment(1.2/50 μs). Installation downstream of type 2 protection. ■Suitable as the final stage of protection in panels with Type 2 protection devices installed upstream. The residual voltage left downstream is less than for Type 1 or 2. They should be installed as close as possible to the equipment being protected. ■Discharge capacity with an 8/20 μs waveform. Imax: 10 kA. ■Exclusive devices for TNS, TNC, TT , IT earthing systems. ■Exclusive devices which are compatible with Power Line Communication networks. ■Biconnect - two types of terminal: for rigid or flexible cable and for fork type comb busbar. ■Available with optional remote signalling.
Dimensions
HS2-10 Power Surge Protector

Contact us